Grid-Interactive Demand Limiting with Python EMS

An openstudio-mcp research demo: authoring, tuning, and evaluating a supervisory controller entirely through MCP tools

Date: 2026-07-07 · Image: openstudio-mcp:dev @ origin/develop 9d76327 (v1.1.0) Interactive dashboard: dr_dashboard.html (self-contained, this directory) · https://claude.ai/code/artifact/4139f7ac-85d0-44b7-9d65-fa53c264c12b Repro assets: this directory (drivers + dashboard HTML) · data regenerated to runs/demo_dr_analysis/*.json Runs: baseline run_demo_dr_baseline_ce6de7f0a0c1 · final run_demo_dr_shed_v3_8953d5dbc6ec


One-slide summary

A custom EnergyPlus Python Plugin ("DemandLimiter") authored via create_python_plugin watches whole-building electric demand every 10 minutes and ratchets all 10 zones' cooling setpoints up in stages (+1/+2/+3 K) whenever demand crosses a shed threshold. Two controller revisions via edit_python_plugin, each driven by simulated evidence. Final result on a 10-zone VAV office in Boston (Jun–Aug):

Metric Baseline Demand-limited (v3) Change
Summer billing peak (30-min basis) 335.2 kW 311.1 kW −7.2%
10-min intervals above 276.9 kW threshold 2,276 610 −73%
Summer electricity (Jun–Aug) 811.7 MWh 779.8 MWh −3.9% (saved)
Demand-charge value @ $15/kW·mo ≈ $1,300 / summer

Demand response that saves energy: raising cooling setpoints during events reduces consumption too, so there is no energy penalty for the peak reduction.

Why researchers should care

  • No custom E+ builds, no IDF hacking, no measure boilerplate: control logic is plain Python attached to the model; the MCP tool wires PythonPlugin:Instance/Variables/ OutputVariable and validates the source against the plugin contract before it ever runs.
  • The controller iteration loop is minutes, not days: author → simulate → query → revise (edit_python_plugin) → re-simulate. Each full 3-month simulation ran in ~10 s on this testbed.
  • Custom telemetry: the plugin publishes its own state (DR Shed Stage) as a normal output variable, queryable alongside standard outputs via query_timeseries.
  • The whole study — model creation, HVAC, weather, control authoring, simulation, extraction — is a reproducible tool-call script (an AI agent can run the entire loop).

Testbed

Item Value
Building 10-zone, 2-story office, 100 m × 50 m (~10,000 m²), core+perimeter zoning (create_baseline_osm)
HVAC ASHRAE baseline System 7: VAV w/ reheat, chiller + boiler plant (add_baseline_system(system_type=7))
Thermostats 21.1 °C heating / 23.9 °C cooling
Weather Boston-Logan TMY3 (change_building_location, sets EPW + design days)
Run period Jun 1 – Aug 31, 10-minute timesteps
Outputs Facility Total Electricity Demand Rate, Zone Mean Air Temperature, Zone Thermostat Cooling Setpoint Temperature, Site OAT (timestep); Electricity:Facility / Cooling / Fans meters (hourly)

Controller (final, v3)

Sensor: Facility Total Electricity Demand Rate (previous timestep — realistic metering lag). Actuators: Zone Temperature Control / Cooling Setpoint per zone (discovered and confirmed with list_ems_actuators). Logic, each zone timestep:

  • Window: 08:00–19:00, every day (building runs 7-day schedules).
  • If demand > threshold (276.9 kW = 82% of true baseline peak): ratchet stage up (never down in-window). 10-min dwell between moves; from idle, jump 2 stages when demand > 115% of threshold (catches the 08:30 startup spike).
  • Stage offsets on the scheduled cooling setpoint: 0 / +1 / +2 / +3 K (23.9 → 24.9 / 25.9 / 26.9 °C). Base setpoint sampled from the schedule whenever unoverridden, so offsets never stack on the controller's own override.
  • After the window: release one stage per 30 min (staggered recovery — no rebound spike).
  • Publishes dr_stage as PythonPlugin:OutputVariable "DR Shed Stage".
  • Guards: handles looked up lazily after api_data_fully_ready, -1 handles raise a severe error and abort; actuation gated on kind_of_sim == 3 so sizing design days are untouched (otherwise the raised setpoints would shrink the autosized plant and corrupt the comparison).

Full source: dr_demo_driver3.py (PLUGIN_TEMPLATE), or get_python_plugin("Demand Limiter") on the saved model runs/demo_dr_shed/model.osm.

Tool workflow (the entire study)

  1. create_baseline_osmload_osm_modellist_thermal_zones
  2. add_baseline_system(system_type=7, thermal_zone_names=[...10 zones])
  3. change_building_location(Boston TMY3)set_run_period(6/1–8/31)
  4. add_output_variable ×4 (timestep) + add_output_meter ×3 (hourly)
  5. save_osm_modelrun_simulationget_run_status (baseline)
  6. query_timeseries → true baseline peak 337.7 kW → threshold = 0.82 × peak
  7. list_ems_actuators(component_type="Zone Temperature Control") — verify per-zone Cooling Setpoint actuator triples from the E+ .edd
  8. create_python_plugin(name="Demand Limiter", template="custom", class_name="DemandLimiter", global_variables=["dr_stage"], output_variable_name="DR Shed Stage")
  9. save_osm_model (plugin script travels in the model's companion files/ dir) → run_simulation
  10. extract_simulation_errors — verify PythonPlugin: Class DemandLimiter imported, zero severe
  11. edit_python_plugin ×2 (revisions below) → rerun
  12. query_timeseries (demand, stage, setpoints, zone temps, OAT, meters) + extract_summary_metrics + extract_end_use_breakdown

The iteration story (the research-workflow payoff)

Rev Controller What the simulation said
v1 Weekdays 13:00–18:00, 3 stages, 30-min dwell Sheds 37–52 kW in-window, but the building peaks at 08:30 (morning pulldown after night setback) — seasonal peak untouched. Also surfaced the design-day/SQL analysis trap (below).
v2 Weekdays 08:00–19:00, 4 stages, 20-min dwell Weekday peaks clipped to ~290 kW; seasonal peak moved to Saturday (329 kW, 6/26) because the model runs 7-day schedules; 20-min staging let the 08:30 spike through at 320 kW.
v3 Every day 08:00–19:00, 10-min dwell, 2-stage jump-start >115% of threshold Billing peak −7.2%; exceedances −73%; energy −3.9%. Residual instantaneous spikes are single-timestep chiller-staging transients.

Results detail

Monthly billing peak (30-min rolling basis, the demand-charge metric):

Month Baseline kW v3 kW Reduction
Jun 335.2 306.0 −8.7%
Jul 333.8 300.2 −10.1%
Aug 335.1 311.1 −7.2%

Monthly facility electricity (MWh): Jun 258.5→251.6, Jul 272.6→259.1, Aug 280.5→269.0.

Peak weekday (Jun 27) anatomy: baseline holds ~324–327 kW from 08:30 to 17:30; controller jump-starts 2 stages on the 08:30 spike (337.7 → 320.6 kW at first trip, one timestep of irreducible metering lag), reaches stage 3 by 09:00, holds ~283–293 kW all day, zone temps float 23.9 → 26.9 °C, and the staggered release (19:00–20:30) returns to schedule with ≤ +5 kW rebound.

Comfort: zones spend event hours up to 26.9 °C. Reported unmet cooling hours improve (152.5 → 24.7 h) — an artifact, not a comfort gain: EnergyPlus scores unmet hours against the actuated setpoint. The honest comfort story is the zone-temperature traces.

Findings a researcher would chase next

  1. Shed capacity is finite: stage 3 floor ≈ 285–295 kW. Deeper cuts need pre-cooling, chiller demand limiting, or lighting/plug DR — all expressible as more plugin logic.
  2. Demand limiting induces plant cycling: brief chiller-staging transients up to +19 kW above baseline for a single timestep. They wash out on a 30-min billing basis; plant-level control (CHW reset, compressor limiting) would remove them.
  3. Feedback-only control cannot preempt step changes: the metered interval that trips the controller is itself the residual peak. Forecast or schedule-aware feed-forward is the fix.
  4. The baseline plant is capacity-limited: baseline zones already float 0.5–1.5 K above setpoint on peak afternoons — why the 351 kW sizing-day plateau never appears in the run period, and a reminder that setpoint-based DR sheds nothing from saturated equipment.

Method caveats / gotchas (worth keeping)

  • Design-day rows in query_timeseries: sizing design days share calendar dates with the run period (Boston: 7/21, 1/21) and are returned blended with run-period rows. Workaround at study time: keep the last row per timestamp (run period simulates last). Since fixed in #88 (closes #87): environment="run_period" is now the default.
  • kind_of_sim guard is mandatory for any plugin that actuates thermostats/setpoints — otherwise sizing runs see the overrides and the plant autosizes smaller.
  • "Billing peak" = max 30-minute rolling average of 10-min instantaneous demand.
  • Custom plugins report one output variable per create_python_plugin call (the first global); design controllers so one state variable + standard E+ outputs tell the story.
  • TMY3 single-year weather; demand-charge $ uses a $15/kW·mo placeholder tariff.

Figure inventory (for slides)

All figures live in the self-contained dashboard (dr_dashboard.html, same as the artifact link). Underlying series JSON regenerated to runs/demo_dr_analysis/:

Figure Data files
Peak-day demand, baseline vs v3, threshold + window band baseline_demand.json, shed3_demand.json (Jun 27 slice)
Controller anatomy: stage step + setpoint/zone-temp traces shed3_peakday.json, baseline_peakday_v2.json
Weekend clip (Sat Jun 26, the v2 miss) baseline_weekend.json, shed3_weekend.json
Monthly billing peaks + monthly energy bars monthly_peaks_w.json, monthly_energy_mwh.json, shed3_monthly_*
Stat tiles (peak, exceedances, energy, $) manifest_v3.json, metrics JSONs

Reproduce

docker build -f docker/Dockerfile -t openstudio-mcp:dev .   # from origin/develop
cd docs/examples/python-ems-demand-response
docker run --rm -v "C:/projects/openstudio-mcp/runs:/runs" -v "$(pwd):/scratch" \
  openstudio-mcp:dev bash -lc "python -u /scratch/dr_demo_driver.py"   # baseline + v1
# driver2/driver3 hardcode the baseline run id printed by driver1 — edit, then run the same way